TD3610 Testing Apparatus for Three-Phase Energy Reference Meters

Product Details
Customization: Available
After-sales Service: Life Time
Warranty: 12 Months Excellent After Service
Shipping & Policy
Shipping Cost: Contact the supplier about freight and estimated delivery time.
Payment Methods:
visa mastercard discover JCB diners club american express T/T
PIX SPEI OXXO PSE OZOW
  Support payments in USD
Secure payments: Every payment you make on Made-in-China.com is protected by the platform.
Refund policy: Claim a refund if your order doesn't ship, is missing, or arrives with product issues.
Manufacturer/Factory
Secured Trading Service
Gold Member Since 2021

Suppliers with verified business licenses

Audited Supplier

Audited by an independent third-party inspection agency

Plant Area
8000 square meters
Management System Certification
ISO9001:2015, ISO14001:2015, ISO45001:2016, Intellectual Property Management System Certificate, ISO 27001:2013
  • TD3610 Testing Apparatus for Three-Phase Energy Reference Meters
  • TD3610 Testing Apparatus for Three-Phase Energy Reference Meters
  • TD3610 Testing Apparatus for Three-Phase Energy Reference Meters
  • TD3610 Testing Apparatus for Three-Phase Energy Reference Meters
  • TD3610 Testing Apparatus for Three-Phase Energy Reference Meters
  • TD3610 Testing Apparatus for Three-Phase Energy Reference Meters
Find Similar Products
  • Overview
  • Company Profile
Overview

Basic Info.

Model NO.
TD3610
Application
Electrical Calibration
Power
Electricity
Voltage Output
/
LCD Display
With LCD Display
Customized
Non-Customized
Accuracy
Class 0.01
Harmonic Output / Measurement
2nd ~ 63st @ 50 Hz / 60 Hz
Temperature coefficient
<0.5 ppm/K
Power Output Stability
0.01% / 2min
Transport Package
Package for Exporting
Trademark
TUNKIA
Origin
China
Production Capacity
1000

Packaging & Delivery

Package Size
100.00cm * 80.00cm * 80.00cm
Package Gross Weight
50.000kg

Product Description

TD3610 Testing Apparatus for Three-Phase Energy Reference Meters
TD3610 Testing Apparatus for Three-Phase Energy Reference Meters

1. Summary

TD3610 is applied for the verification of three-phase energy reference standard. It mainly consists of three-phase precision standard power source, class 0.01 three-phase standard watt-hour meter, measurement and control platform, PC(optional) and verification software. TD3610 can automatically complete the class 0.02 and the following class of R46 AC standard electricity meter or AC standard source verification.
 

2. Features

  1. High accuracy: Accuracy class 0.01, output power stability is 0.01% / 2min.
  2. High reliability: Automatic range switching. It can guarantee the measurement accuracy even when the machine is switched on and off in the limit state (500 V, 100 A). 
  3. Reliable quality: Temperature coefficient <0.5 ppm/K.
  4. Harmonic output / measurement: The 2nd ~ 63st @ 50 Hz / 60 Hz, Harmonic content and phase are programmable.
  5. Two sets of test buttons: The device has a set of output and measurement buttons, which are independent of each other.
  6. Electric energy measurement: Equipped with single phase, three phase three wire, three phase four wire, positive phase sequence, reverse sequence (contain negative direction) and other power metering functions.
  7. Comprehensive analysis function: Waveform display, phase diagram display, Stability test, Change curve drawing, Statistical analysis of data, etc.
  8. Mobile measurement and control console: Users can read or control output value through LCD touch screen.
 

3. Specifications

3.1 Voltage / Current

Power Range Resolution Accuracy
±(ppm of reading + ppm of range) [1]
Temperature Coefficient@ (15~30)°C
±(ppm of reading + ppm of range) /°C
AC Voltage 60 V 10 μV 30 + 20 0.25 + 0.25
120 V 0.1 mV 30 + 20 0.25 + 0.25
240 V 0.1 mV 30 + 20 0.25 + 0.25
480 V 0.1 mV 30 + 20 0.25 + 0.25
AC Current 5 mA 1 nA 120 + 80 5 + 5
10 mA 10 nA 60 + 40 3 + 3
20 mA 10 nA 60 + 40 0.75 + 0.75
50 mA 10 nA 30 + 20 0.25 + 0.25
100 mA 0.1 μA 30 + 20 0.25 + 0.25
200 mA 0.1 μA 30 + 20 0.25 + 0.25
500 mA 0.1 μA 30 + 20 0.25 + 0.25
1 A 1 μA 30 + 20 0.25 + 0.25
2 A 1 μA 30 + 20 0.25 + 0.25
5 A 1 μA 30 + 20 0.25 + 0.25
10 A 10 μA 30 + 20 0.25 + 0.25
20 A 10 μA 30 + 20 0.25 + 0.25
50 A 10 μA 30 + 20 0.25 + 0.25
100 A 0.1 mA 30 + 20 0.25 + 0.25
Note [1] : (ppm = parts per million) (e.g., 10ppm = 0.001%).
  1. Voltage/ Current Output / measurement range: 6 V~576 V, 0.2 mA~120 A,7-digits display
  2. Symmetry: Voltage ≤ 0.2%, Current ≤ 0.5%, Phase ≤ 0.5°
  3. Voltage Output max burden: 45VA / (per phase)
  4. Current Output max burden:90VA / (per phase)
  5. Protective function: Short-circuit protection, Open-circuit protection, Overload protection

3.2 Frequency / Phase

Type Range of Regulation Optimal Accuracy of Measurement
Frequency 45.000 00 Hz~65.000 00 Hz 50 ppm*RD
Phase 0.000 0°~359.999 9°
(I ≥ 50mA)
0.003°
 

3.3 Power / Electrical energy

Output / Measurement Voltage Range Current Range Power Factor Accuracy ±(% of reading)
45Hz ≤ F ≤ 65Hz
Power / Electrical energy measurement 30 V ≤ U ≤ 480 V 50 mA ≤ I ≤120 A 0.5L~1~0.5C 0.01%*RD
10 mA ≤ I < 50 mA 1 0.01%*RD
0.5L~1~0.5C 0.02%*RD
3 mA ≤ I < 10 mA 1 0.02%*RD
0.5L~1~0.5C 0.04%*RD
0.2 mA ≤ I < 3 mA 1 0.02%*RD×3mA/I
  1. Output power stability: 0.01% / 2min;
  2. Measuring range of power/energy: Combination of AC voltage and AC current range;
  3. Power factor Measurement range: -1.000 00…0.000 00…1.000 00;
  4. Standard electric energy pulse output: High frequency pulse output port outputs 60KHz at full range, low frequency pulse output port outputs 6Hz at full range;
  5. Standard energy pulse input: Frequency ≤ 200 kHz, Voltage: 0...3.3 V...24 V
  6. Electric energy error display: Automatic, resolution is 0.0001%.
 

4. General Specifications

Power Supply AC ( 220 ± 22 ) V, ( 50 ± 2 ) Hz
Warm Up time 30 min
Temperature Performance Storage temperature: 5°C~45°C
Operating temperature: -10°C~55°C  
Humidity Performance Operating humidity: < 80% @ 30°C, < 70% @ 40°C, < 40% @ 50°C
Storage humidity: (20%~80%) R·H, non-condensing
Elevation < 3000 m
Communication Interface RS232, LAN

Company Profile
 

TD3610 Testing Apparatus for Three-Phase Energy Reference Meters

TD3610 Testing Apparatus for Three-Phase Energy Reference MetersTD3610 Testing Apparatus for Three-Phase Energy Reference Meters

 

Send your message to this supplier

*From:
*To:
*Message:

Enter between 20 to 4,000 characters.

This is not what you are looking for? Post a Sourcing Request Now
Contact Supplier