• TD4500 Calibrator for AC Sampling Devices and Transmitters
  • TD4500 Calibrator for AC Sampling Devices and Transmitters
  • TD4500 Calibrator for AC Sampling Devices and Transmitters
  • TD4500 Calibrator for AC Sampling Devices and Transmitters
  • TD4500 Calibrator for AC Sampling Devices and Transmitters
  • TD4500 Calibrator for AC Sampling Devices and Transmitters

TD4500 Calibrator for AC Sampling Devices and Transmitters

Application: Electromagnetic Instrument
Power: Electricity
Customized: Non-Customized
Customization:
Shipping Cost:

Estimated freight per unit.

about shipping cost and estimated delivery time.
Payment Method: visa mastercard discover JCB diners club american express T/T
  Initial Payment Full Payment
Currency: US$
Return&refunds: You can apply for a refund up to 30 days after receipt of the products.
From payment to delivery, we protect your trading.
TD4500 Calibrator for AC Sampling Devices and Transmitters pictures & photos
TD4500 Calibrator for AC Sampling Devices and Transmitters
US $14,000-17,700 / Piece
Min. Order: 1 Piece
Gold Member Since 2021

Suppliers with verified business licenses

Secured Trading Service
Manufacturer/Factory
  • Overview
  • Company Profile
Overview

Basic Info.

Model NO.
TD4500
Accuracy class
0.02, 0.05
3PH AC voltage output
6 V~456 V
3PH AC current output
0.1 A~6.25 A
3PH voltage meter
6 V~456 V
3PH current meter
0.1 A~6 A
Frequency
45 Hz~70 Hz
DC voltage output
10 mV~330 V
DC current output
0.1 mA~22 mA
Harmonic output
2nd~21th
Transport Package
Package for Exporting
Specification
17kg; 435 mm(W) x 415 mm(D) x 195 mm(H)
Trademark
TUNKIA
Origin
China
Production Capacity
1000

Packaging & Delivery

Package Size
50.00cm * 50.00cm * 25.00cm
Package Gross Weight
23.000kg

Product Description

TD4500 Calibrator for AC Sampling Devices and Transmitters
TD4500 Calibrator for AC Sampling Devices and Transmitters

1. Summary

TD4500 is a multi-function 3PH power calibrator. Class 0.02 / class 0.05 available. It integrates AC/DC power output function, 3PH measuring function, harmonic function, transmitter test function, U4th voltage output function, AC energy meter test function. Can be used to calibrate AC/DC voltmeter, AC/DC ammeter, AC/DC power meter and transmitter, etc.
 

2. Features

  1. 3PH AC voltage output:6 V~456 V
  2. 3PH AC current output:0.1 A~6.25 A
  3. 3PH voltage meter:6 V~456 V;
  4. 3PH current meter:0.1 A~6 A
  5. Frequency:45 Hz~70 Hz
  6. U-I phase:~360°
  7. DC voltage output:10 mV~330 V
  8. DC current output:0.1 mA~22 mA
  9. Accuracy class: 0.02, 0.05.
  10. 2nd~21st harmonic output
  11. Transmitter test function
  12. U4 AC voltage output function
  13. Test software(option)
 

3. Application

TD4500 Calibrator for AC Sampling Devices and Transmitters

 

4. Characteristics

Wide Output
TD4500 Calibrator for AC Sampling Devices and Transmitters
  1. It can meet most single-phase / three-phase meters or DC meters.
 
Wide Input
TD4500 Calibrator for AC Sampling Devices and Transmitters
  1. It can meet most single-phase / three-phase source.


 
Multiple Output Mode
 TD4500 Calibrator for AC Sampling Devices and Transmitters
  1. "Direct output"mode,User can set output value by physical key or touch screen.
  2. Three-phase unit adjustment or single phase adjustment.
TD4500 Calibrator for AC Sampling Devices and Transmitters
  1. "Rotary Knob"mode,User can setting in clockwise direction or anticlockwise direction.


 
Multiple Output Mode
TD4500 Calibrator for AC Sampling Devices and Transmitters
  1. Touch "Calibration point"of screen for "% setting".




 

Graphics Features
TD4500 Calibrator for AC Sampling Devices and Transmitters
S/N Function declaration2
1 Oscilloscope function,user can observe voltage and current waves.
2 Precise display phase for voltage and current.
3 Trend variation display.


 

Harmonics Function
S/N Function declaration
1 Set amplitude of harmonic.
2 Set phase of harmonic(fundamental wave).
3 Choose 2nd~21st harmonics channel output.
4 Oscilloscope function, user can observe voltage and current waves.
5 Display frequency spectrum of harmonic by histogram.(fundament wave is 100%)
 

5. Specifications

5.1 Three-Phase Voltage / Current Output

Voltage Range Resolution Stability
( %/min )
Accuracy
±(ppm of reading + ppm of range) [1]
Max
Burden (mA)
Class 0.05 Class 0.02 Class 0.05 Class 0.02
57.7 V 0.1 mV 0.01 0.005 300 + 200 120 + 80 250
100 V 1 mV 0.01 0.005 300 + 200 120 + 80 150
220 V 1 mV 0.01 0.005 300 + 200 120 + 80 60
380 V 1 mV 0.01 0.005 300 + 200 120 + 80 40
Note [1] : (ppm = parts per million) (e.g.,10ppm = 0.001%).
 
Current Range Resolution Stability
( %/min )
Accuracy
±(ppm of reading + ppm of range) [1]
Max
Burden (V)
Class 0.05 Class 0.02 Class 0.05 Class 0.02
1 A 10 μA 0.01 0.005 300 + 200 120 + 80 12
5 A 10 μA 0.01 0.005 300 + 200 120 + 80 3
  1. Three-phase voltage output:6 V~456 V,Degree of distortion:<0.2%
  2. Three-phase current output:0.1 A~6.25 A,Degree of distortion:<0.2%
  3. Voltage short circuit, current open-circuit and overload protection
 

5.2 Frequency / Phase / Harmonic

Symmetry Voltage superior to 0.2%;Current superior to 0.5%;Phase superior to 0.5°
Frequency Range:45 Hz~70 Hz;
Adjustment fineness:0.001 Hz;
Accuracy:±0.02 Hz (class 0.05), ±0.01 Hz(class 0.02)
Phase Range:0.000 0°~359.999 9°;
Adjustment fineness:0.001°;
Accuracy:±0.02° (class 0.05), ±0.01°(class 0.02)
Harmonic 2nd~21st harmonic;
Amplitude 0~25% adjustable;
Phase 0~359.99°adjustable
 

5.3 Three-Phase Power Output

Current Range Stability
( %/min )
Accuracy
( ± %*FS)[2]
Class 0.05 Class 0.02 Class 0.05 Class 0.02
Active power |cosφ|≥0.5 0.01 0.005 0.05 0.02
Reactive power |sinφ|≥0.5 0.02 0.01 0.1 0.05
Apparent power 0.02 0.01 0.1 0.05
Power factor 0.02 0.01 0.1 0.05
Note [2] :FS= voltage range ×current range
  1. Power factor setting range:-1.000 000…0.000 000…1.000 000
 

5.4 Three-Phase Voltage / Current Input

Type Range Resolution Accuracy
±(ppm of reading + ppm of range) [1]
Direct Input Clamp Current Input [3]
AC Voltage
ACV
57.7 V 0.1 mV 300 + 200 --
100 V 1 mV 300 + 200 --
220 V 1 mV 300 + 200 --
380 V 1 mV 300 + 200 --
AC Current
ACI
1 A 10 μA 300 + 200 --
5 A 10 μA 300 + 200 0.2%*RG
Note [3]:Clamp is option,if it be need, it must remark in order contract,Same as below.
  1. Voltage input:6 V~456 V,Current input:0.1 A~6 A
  2. Frequency:45 Hz~70 Hz,Accuracy:± 0.01 Hz
  3. Phase:0.000°~359.999°,Accuracy:± 0.02°

5.5 Three-Phase Power Input

Type Accuracy
Direct Input Clamp Current Input
Active power ± 0.05%*FS ± 0.2%*FS
Reactive power ± 0.1%*FS ± 0.5%*FS
Apparent power ± 0.1%*FS ± 0.5%*FS
Power factor ± 0.1% ± 0.5%
 

5.6 DC Voltage / Current Output

Voltage Range Resolution Stability
( %/min )
Accuracy
±(ppm of reading + ppm of range) [1]
Max
Burden (mA)
Class 0.05 Class 0.02 Class 0.05 Class 0.02
75 mV 0.1 μV 0.005 0.005 300 + 200 120 + 80 10
1 V 10 μV 0.005 0.005 300 + 200 120 + 80 10
10 V 0.1 mV 0.005 0.005 300 + 200 120 + 80 10
30 V 0.1 mV 0.005 0.005 300 + 200 120 + 80 500
100 V 1 mV 0.005 0.005 300 + 200 120 + 80 150
300 V 1 mV 0.005 0.005 300 + 200 120 + 80 50
 
Current Range Resolution Stability
( %/min )
Accuracy
±(ppm of reading + ppm of range) [1]
Max
Burden (V)
Class 0.05 Class 0.02 Class 0.05 Class 0.02
1 mA 10 nA 0.01 0.005 300 + 200 120 + 80 10
5 mA 10 nA 0.01 0.005 300 + 200 120 + 80 10
20 mA 100 nA 0.01 0.005 300 + 200 120 + 80 10
  1. DC voltage output:10 mV~330 V,ripple factor:< 1%;
  2. DC current output:0.1 mA~22 mA,ripple factor:< 1%
  3. Voltage short circuit, current open-circuit and overload protection

5.7 DC Meter(Transmitter)

Range Measurement Range Accuracy Measurement Range of Ripple Accuracy of Ripple
1 V ± ( 0~1.2 ) V ± 0.01%*RG 0~30 mV ± 1 mV
10 V ± ( 0~12 ) V ± 0.01%*RG 0~300 mV ± 10 mV
2 mA ±( 0~2.4) mA ± 0.01%*RG 0~60 μA ± 2 μA
20 mA ± ( 0~24 ) mA ± 0.01%*RG 0~600 μA ± 20 μA
  1. Response time:measurement range:0~1000 ms,accuracy:± 40 ms

5.8 U4 Voltage Output(option)

  1. Voltage range:100 V,380 V
  2. Output range:(0~110)%*RG
  3. Accuracy of measurement ( k = 2 ):± 0.05%*RG
  4. Max output power:10 VA
  5. Frequency range:45 Hz~55 Hz
  6. The function is used to test Synchrometer .

6. General Specifications

Power Supply AC ( 220 ± 22 ) V,( 50 ± 2 ) Hz
Temperature Performance Working temperature:0°C~45°C;
Storage temperature:-20°C~70°C
Humidity Performance Working humidity:< 80% @ 30°C,< 70% @ 40°C,< 40% @ 50°C
Storage humidity:(20%~80%) R·H,non-condensing
Interface RS232
 

7. Ordering Information

TD4500 Calibrator for AC Sampling Devices and Transmitters
 
Company Profile
 

TD4500 Calibrator for AC Sampling Devices and Transmitters

TD4500 Calibrator for AC Sampling Devices and TransmittersTD4500 Calibrator for AC Sampling Devices and Transmitters

 

Send your message to this supplier

*From:
*To:
*Message:

Enter between 20 to 4,000 characters.

This is not what you are looking for? Post a Sourcing Request Now

You Might Also Like

From payment to delivery, we protect your trading.
TD4500 Calibrator for AC Sampling Devices and Transmitters pictures & photos
TD4500 Calibrator for AC Sampling Devices and Transmitters
US $14,000-17,700 / Piece
Min. Order: 1 Piece
Gold Member Since 2021

Suppliers with verified business licenses

Secured Trading Service
Manufacturer/Factory
Plant Area
8000 square meters
Management System Certification
ISO9001:2015, ISO14001:2015, ISO45001:2016, Intellectual Property Management System Certificate, ISO 27001:2013