TD4530 Three-Phase and DC Field Calibrator

Application: Electromagnetic Instrument
Power: Electricity
Customized: Non-Customized
Customization:
Shipping Cost:

Estimated freight per unit.

about shipping cost and estimated delivery time.
Payment Method: visa mastercard discover JCB diners club american express T/T
  Initial Payment Full Payment
Currency: US$
Return&refunds: You can apply for a refund up to 30 days after receipt of the products.
From payment to delivery, we protect your trading.
TD4530 Three-Phase and DC Field Calibrator pictures & photos
TD4530 Three-Phase and DC Field Calibrator
US $16,500-20,000 / Set
Min. Order: 1 Set
Gold Member Since 2021

Suppliers with verified business licenses

Secured Trading Service
Manufacturer/Factory
  • Overview
  • Company Profile
Overview

Basic Info.

Model NO.
TD4530
Accuracy class
0.02, 0.05
3PH AC voltage output
1 V~660 V
3PH AC current output
20 mA~30 A
3PH voltage meter
0.1 A~6 A
Frequency
45 Hz~70 Hz
DC voltage output
10 mV~1100 V
DC current output
0.1 mA~30 A
Harmonic output
2nd~21th
Transport Package
Package for Exporting
Specification
22kg; 470 mm(W) x 470 mm(D) x 190 mm(H)
Trademark
TUNKIA
Origin
China
Production Capacity
1000

Packaging & Delivery

Package Size
60.00cm * 60.00cm * 25.00cm
Package Gross Weight
30.000kg

Product Description

TD4530 Three-Phase and DC Field Calibrator
TD4530 Three-Phase and DC Field Calibrator

1. Summary

TD4530 is a multi-function 3PH power calibrator. Class 0.02 / class 0.05 available. It integrates AC/DC power output function, 3PH measuring function, harmonic function, transmitter test function, U4th voltage output function, AC energy meter test function. Can be used to calibrate AC/DC voltmeter, AC/DC ammeter, AC/DC power meter electric energy meter and transmitter, etc.
 

2. Features

  1. 3PH AC voltage output:1 V~660 V (UAB Max 1100 V)
  2. 3PH AC current output:20 mA~30 A
  3. 3PH voltage meter:6 V~456 V;
  4. 3PH current meter:0.1 A~6 A
  5. Frequency:45 Hz~70 Hz
  6. U-I phase:~360°
  7. DC voltage output:10 mV~1100 V
  8. DC current output:0.1 mA~30 A
  9. Accuracy class: 0.02, 0.05.
  10. 2nd~21st harmonic output
  11. Transmitter test function
  12. U4th AC voltage output function(option)
  13. Energy meter test function(option)
  14. Test software(option)
 

3. Application

TD4530 Three-Phase and DC Field Calibrator

 

4. Characteristics

Wide Output
TD4530 Three-Phase and DC Field Calibrator
  1. It can meet most single-phase / three-phase meters or DC meters.
 
Wide Input
TD4530 Three-Phase and DC Field Calibrator
  1. It can meet most single-phase / three-phase source.


 
Multiple Output Mode
TD4530 Three-Phase and DC Field Calibrator
  1. "Direct output"mode,User can set output value by physical key or touch screen.
  2. Three-phase unit adjustment or single phase adjustment.
TD4530 Three-Phase and DC Field Calibrator
  1. "Rotary Knob"mode,User can setting in clockwise direction or anticlockwise direction.
.
 
Multiple Output Mode
TD4530 Three-Phase and DC Field Calibrator
  1. Touch "Calibration point"of screen for "% setting".
  1. "Remote Control Box(option)",by operation of coarse tuning-fine tuning,can calibrate analog meter.




 

Harmonics Function
TD4530 Three-Phase and DC Field Calibrator
S/N Function declaration
1 Set amplitude of harmonic.
2 Set phase of harmonic(fundamental wave).
3 Choose 2nd~21st harmonics channel output.
4 Oscilloscope function, user can observe voltage and current waves.
5 Display frequency spectrum of harmonic by histogram.(fundament wave is 100%)

5. Specifications

5.1 Three-Phase Voltage / Current Output

Voltage Range Resolution Stability
( %/min )
Accuracy
±(ppm of reading + ppm of range) [1]
Max
Burden (mA)
Class 0.05 Class 0.02 Class 0.05 Class 0.02
15 V 0.1 mV 0.01 0.005 300 + 200 120 + 80 500
30 V 0.1 mV 0.01 0.005 300 + 200 120 + 80 500
60 V 0.1 mV 0.01 0.005 300 + 200 120 + 80 150
75 V 0.1 mV 0.01 0.005 300 + 200 120 + 80 150
150 V 1 mV 0.01 0.005 300 + 200 120 + 80 50
300 V 1 mV 0.01 0.005 300 + 200 120 + 80 50
600 V 1 mV 0.01 0.005 300 + 200 120 + 80 25
750 V[2] 1 mV 0.01 0.005 300 + 200 120 + 80 25
1000 V[2] 10 mV 0.01 0.005 300 + 200 120 + 80 25
Note [1] : (ppm = parts per million) (e.g.,10ppm = 0.001%). Note [2]:750 V,1000 V as UAB.
 
Current Range Resolution Stability
( %/min )
Accuracy
±(ppm of reading + ppm of range) [1]
Max
Burden (V)
Class 0.05 Class 0.02 Class 0.05 Class 0.02
200 mA 1 μA 0.01 0.005 300 + 200 120 + 80 50
500 mA 1 μA 0.01 0.005 300 + 200 120 + 80 20
1 A 10 μA 0.01 0.005 300 + 200 120 + 80 20
2 A 10 μA 0.01 0.005 300 + 200 120 + 80 5
5 A 10 μA 0.01 0.005 300 + 200 120 + 80 5
10 A 0.1 mA 0.01 0.005 300 + 200 120 + 80 1
25 A 0.1 mA 0.01 0.005 300 + 200 120 + 80 1
  1. Three-phase voltage output: 1 V~660 V(UAB Max 1100 V), Degree of distortion:< 0.5%
  2. Three-phase current output:20 mA~30 A,Degree of distortion:< 0.2%;
  3. Voltage short circuit, current open-circuit and overload protection

5.2 Frequency / Phase / Harmonic

Symmetry Voltage superior to 0.2%;Current superior to 0.5%;Phase superior to 0.5°
Frequency Range:45 Hz~70 Hz;
Adjustment fineness:0.001 Hz;
Accuracy:±0.02 Hz (class 0.05), ±0.01 Hz(class 0.02)
Phase Range:0.000 0°~359.999 9°;
Adjustment fineness:0.001°;
Accuracy:±0.02° (class 0.05), ±0.01°(class 0.02)
Harmonic 2nd~21st harmonic;
Amplitude 0~25% adjustable;
Phase 0~359.99°adjustable
 

5.3 Three-Phase Power Output

Current Range Stability
( %/min )
Accuracy
( ± %*FS)[2]
Class 0.05 Class 0.02 Class 0.05 Class 0.02
Active power |cosφ|≥0.5 0.01 0.005 0.05 0.02
Reactive power |sinφ|≥0.5 0.02 0.01 0.1 0.05
Apparent power 0.02 0.01 0.1 0.05
Power factor 0.02 0.01 0.1 0.05
Note [2] :FS= voltage range ×current range
  1. Power factor setting range:-1.000 000…0.000 000…1.000 000
 

5.4 Three-Phase Voltage / Current Input

Type Range Resolution Accuracy
±(ppm of reading + ppm of range) [1]
Direct Input Clamp Current Input [3]
AC Voltage
ACV
57.7 V 0.1 mV 300 + 200 --
100 V 1 mV 300 + 200 --
220 V 1 mV 300 + 200 --
380 V 1 mV 300 + 200 --
AC Current
ACI
1 A 10 μA 300 + 200 --
5 A 10 μA 300 + 200 0.2%*RG
Note [3]:Clamp is option,if it be need, it must remark in order contract,Same as below.
  1. Voltage input:6 V~456 V,Current input:0.1 A~6 A
  2. Frequency:45 Hz~70 Hz,Accuracy:± 0.01 Hz
  3. Phase:0.000°~359.999°,Accuracy:± 0.02°
 

5.5 Three-Phase Power Input

Type Accuracy
Direct Input Clamp Current Input
Active power ± 0.05%*FS ± 0.2%*FS
Reactive power ± 0.1%*FS ± 0.5%*FS
Apparent power ± 0.1%*FS ± 0.5%*FS
Power factor ± 0.1% ± 0.5%
 

5.6 DC Voltage / Current Output

Voltage Range Resolution Stability
( %/min )
Accuracy
±(ppm of reading + ppm of range) [1]
Max
Burden (mA)
Class 0.05 Class 0.02 Class 0.05 Class 0.02
100 mV 1 μV 0.005 0.005 300 + 200 120 + 120 10
1 V 10 μV 0.005 0.005 300 + 200 120 + 80 10
10 V 0.1 mV 0.005 0.005 300 + 200 120 + 80 10
30 V 0.1 mV 0.005 0.005 300 + 200 120 + 80 500
100 V 1 mV 0.005 0.005 300 + 200 120 + 80 150
300 V 1 mV 0.005 0.005 300 + 200 120 + 80 50
600 V 10 mV 0.005 0.005 300 + 200 120 + 80 25
1000 V 10 mV 0.005 0.005 300 + 200 120 + 80 15
 
Current Range Resolution Stability
( %/min )
Accuracy
±(ppm of reading + ppm of range) [1]
Max
Burden (V)
Class 0.05 Class 0.02 Class 0.05 Class 0.02
100 μA 1 nA 0.01 0.005 300 + 200 120 + 80 10
1 mA 10 nA 0.01 0.005 300 + 200 120 + 80 10
10 mA 0.1 μA 0.01 0.005 300 + 200 120 + 80 10
100 mA 1 μA 0.01 0.005 300 + 200 120 + 80 10
1A 10 μA 0.01 0.005 300 + 200 120 + 80 10
3A 10 μA 0.01 0.005 300 + 200 120 + 80 10
10A 100 μA 0.01 0.005 300 + 200 120 + 80 10
25A 100 μA 0.01 0.005 300 + 200 120 + 80 10
  1. DC voltage output:10 mV~1100 V,ripple factor:< 1%;
  2. DC current output:0.1 mA~30 A,ripple factor:< 1%
  3. Voltage short circuit, current open-circuit and overload protection

5.7 DC Meter(Transmitter)

Range Measurement Range Accuracy Measurement Range of Ripple Accuracy of Ripple
1 V ± ( 0~1.2 ) V ± 0.01%*RG 0~30 mV ± 1 mV
10 V ± ( 0~12 ) V ± 0.01%*RG 0~300 mV ± 10 mV
2 mA ±( 0~2.4) mA ± 0.01%*RG 0~60 μA ± 2 μA
20 mA ± ( 0~24 ) mA ± 0.01%*RG 0~600 μA ± 20 μA
  1. Response time:measurement range:0~1000 ms,accuracy:± 40 ms
 

5.8 Test Energy Meter(option)

Type Accuracy
Class 0.05 Class 0.02
Active electrical energy ± 0.1%*reading ± 0.05%* reading
Reactive electrical energy ± 0.2%* reading ± 0.1%* reading
  1. Energy pulse output:full range for 60 kHz
  2. Energy pulse input:max frequency is 1 kHz,pulse level:3 V~12 V
  3. Constant setting of Electrical energy meter:1…1000000 imp./kwh or 1…1000000 imp./ws
 

5.9 U4th Voltage Output(option)

  1. Voltage range:100 V,380 V
  2. Output range:(0~110)%*RG
  3. Accuracy:± 0.05%*RG
  4. Max output power:10 VA
  5. Frequency range:45 Hz~55 Hz
  6. The function is used to test Synchrometer.
 

6. General Specifications

Power Supply AC ( 220 ± 22 ) V,( 50 ± 2 ) Hz
Temperature Performance Working temperature:0°C~45°C;
Storage temperature:-20°C~70°C
Humidity Performance Working humidity:< 80% @ 30°C,< 70% @ 40°C,< 40% @ 50°C
Storage humidity:(20%~80%) R·H,non-condensing
Interface RS232
 

7. Ordering Information


TD4530 Three-Phase and DC Field Calibrator
 
Company Profile
 

TD4530 Three-Phase and DC Field Calibrator

TD4530 Three-Phase and DC Field CalibratorTD4530 Three-Phase and DC Field Calibrator

Send your message to this supplier

*From:
*To:
*Message:

Enter between 20 to 4,000 characters.

This is not what you are looking for? Post a Sourcing Request Now

You Might Also Like

From payment to delivery, we protect your trading.
TD4530 Three-Phase and DC Field Calibrator pictures & photos
TD4530 Three-Phase and DC Field Calibrator
US $16,500-20,000 / Set
Min. Order: 1 Set
Gold Member Since 2021

Suppliers with verified business licenses

Secured Trading Service
Manufacturer/Factory
Plant Area
8000 square meters
Management System Certification
ISO9001:2015, ISO14001:2015, ISO45001:2016, Intellectual Property Management System Certificate, ISO 27001:2013