• TUNKIA TH3600 three-phase Energy Meters Calibrator Broadband Low Current Standard Power Source
  • TUNKIA TH3600 three-phase Energy Meters Calibrator Broadband Low Current Standard Power Source
  • TUNKIA TH3600 three-phase Energy Meters Calibrator Broadband Low Current Standard Power Source
  • TUNKIA TH3600 three-phase Energy Meters Calibrator Broadband Low Current Standard Power Source
  • TUNKIA TH3600 three-phase Energy Meters Calibrator Broadband Low Current Standard Power Source
  • TUNKIA TH3600 three-phase Energy Meters Calibrator Broadband Low Current Standard Power Source

TUNKIA TH3600 three-phase Energy Meters Calibrator Broadband Low Current Standard Power Source

After-sales Service: 24 Hours
Warranty: 1 year
Application: Electromagnetic Instrument, Electrical Calibrator
Customization:
Shipping Cost:

Estimated freight per unit.

about shipping cost and estimated delivery time.
Payment Method: visa mastercard discover JCB diners club american express T/T
  Initial Payment Full Payment
Currency: US$
Return&refunds: You can apply for a refund up to 30 days after receipt of the products.
From payment to delivery, we protect your trading.
TUNKIA TH3600 three-phase Energy Meters Calibrator Broadband Low Current Standard Power Source pictures & photos
TUNKIA TH3600 three-phase Energy Meters Calibrator Broadband Low Current Standard Power Source
US $1,000-80,000 / Piece
Min. Order: 1 Piece
Gold Member Since 2021

Suppliers with verified business licenses

Secured Trading Service
Manufacturer/Factory
  • Overview
  • Company Profile
Overview

Basic Info.

Model NO.
TH3600
Power
Electricity
LCD Display
With LCD Display
Customized
Non-Customized
Accuracy Class
0.005 (50 ppm) / 0.01(100 ppm)
Maximum Voltage Output
528 V
Maximum Current Output
120 mA
Minimum current output
20μA
Harmonic function (optional)
2nd to 63rd
Power Supply
AC ( 220 ± 22 ) V, ( 50 ± 2 ) Hz
Communication Interface
RS232, LAN
Transport Package
Package for Exporting
Trademark
TUNKIA
Origin
China
Production Capacity
100

Packaging & Delivery

Package Size
50.00cm * 50.00cm * 50.00cm
Package Gross Weight
30.000kg

Product Description

 
TH3600 Broadband Low Current Standard Power Source
 
1.Summary

TH3600 is a three-phase standard power source with wide frequency and low current output. The output bandwidth is 45 Hz~1kHz, and the low current output can be as low as 20μA. It can be used as a power/energy calibration source for high-precision current measurement and analysis below 120mA. It makes up for the serious shortcomings of traditional electric energy meter calibration devices in broadband and low current measurement. It has optional power accuracy of class 0.005 and 0.01.

2.Features
  1. Maximum output: 528 V / 120 mA, which can ensure the stability of value output under full load conditions.
  2. Minimum current output: as low as 20μA.
  3. Multi-functional electric energy measurement: It has forward, reverse active and reactive energy, and supports the calibration of electric energy meters.
  4. Harmonic function (optional): Can load 2nd to 63rd harmonics with adjustable amplitude and phase to complete the harmonic impact test.
3. Specification

3.1 ACV Output

Range Resolution Load Capacity Short-term Stability 
( ppm / min )
Measurement Uncertainty
 ( ppm*RD+ppm*RG,45Hz~65Hz)
Total Harmonic Distortion
(THD, % )
Class 0.005 Class 0.01 Class 0.005 Class 0.01
60 V 0.01 mV 0.3A 5 10 12 + 8 25 + 15 < 0.01
120 V 0.1 mV 0.15A 5 10 12 + 8 25 + 15 < 0.01
240 V 0.1 mV 0.08A 5 10 12 + 8 25 + 15 < 0.01
480 V 0.1 mV 0.04A 5 10 12 + 8 25 + 15 < 0.01
  1. Output range: 6 V ~ 528 V, 7-digit display
  2. Adjustment fineness: 3ppm
  3. Protection functions: short circuit protection, overload protection, temperature protection
 

3.2 ACI Output

Range Resolution Load Capacity Short-term Stability
( ppm / min )
Measurement Uncertainty 
 ( ppm*RD+ppm*RG,45Hz~65Hz)
Total Harmonic Distortion
(THD, % )
Class 0.005 Class 0.01 Class 0.005 Class 0.01
0.2 mA 0.1 nA 8V 12 20 30 + 20 50 + 30 < 0.02
0.5 mA 0.1 nA 8V 12 20 30 + 20 50 + 30 < 0.02
1 mA 1 nA 8V 8 15 20 + 10 30 + 20 < 0.02
2 mA 1 nA 8V 8 15 20 + 10 30 + 20 < 0.01
5 mA 1 nA 8V 8 15 20 + 10 30 + 20 < 0.01
10 mA 10 nA 8V 8 15 20 + 10 30 + 20 < 0.01
20 mA 10 nA 8V 8 15 20 + 10 30 + 20 < 0.01
50 mA 10 nA 8V 8 15 20 + 10 30 + 20 < 0.01
100 mA 100 nA 8V 8 15 20 + 10 30 + 20 < 0.01
  1. Output range: 0.02 mA~120 mA, 7-digit display
  2. Adjustment fineness: 3ppm
  3. Protection functions: open circuit protection, overload protection, temperature protection
 

3.3 Frequency / Phase

Parameter Adjustment Range Optimal Measurement Uncertainty (k=2)
Frequency 45.0000 Hz~1000.000 Hz 50 ppm*RD
Phase 0.000 0°~359.999 9° 0.001°
Harmonic (optional) 2nd~63rd, amplitude 0~40% (total harmonic distortion does not exceed 50%), phase adjustable from 0.0°~ 359.99°
 

3.4 Power / Energy

Measured Power Voltage Range Current Range Measurement Uncertainty
(45Hz~65Hz,k=2)
Class 0.005 Class 0.01
Active Power / Energy
Apparent Power
|cosj| ≥ 0.5
30 V ≤ U ≤ 480 V 0.05 mA ≤ I <1 m A 0.005%*FS 0.01%*FS
1 mA ≤ I < 100 mA 0.005%*RD 0.01%*RD
Reactive Power
|sinj| ≥ 0.5
30 V ≤ U ≤ 480 V 0.05 mA ≤ I <1 m A 0.01%*FS 0.02%*FS
1 mA ≤ I < 100 mA 0.01%*RD 0.02%*RD
Power Factor 30 V ≤ U ≤ 480 V 0.05 mA ≤ I <1 m A 0.01% 0.02%
1 mA ≤ I < 100 mA 0.005% 0.01%
Note: FS = voltage range value × current range value
  1. Power/electric energy measurement range: combination of AC voltage range and AC current range
  2. Power factor measurement range: -1.000 00…0.000 00…1.000 00
  3. Standard electric energy pulse output: high frequency full scale value corresponds to 60 kHz, low frequency full scale value corresponds to 6 Hz
  4. Standard power pulse input: frequency ≤ 200 kHz, voltage: 0…3.3 V…24 V
  5. Power error display: automatic, resolution 0.0001%
 
4.General Specification
Power Supply AC ( 220 ± 22 ) V, ( 50 ± 2 ) Hz
Preheat Time 30mins
Temperature Performance Working temperature: 15°C~30°C;
Storage temperature: -10°C~55°C
Humidity Performance Working humidity: < 80% @ 30°C, < 70% @ 40°C, < 40% @ 50°C
Storage humidity: (20%~80%) R·H, non-condensing
Communication Interface RS232,LAN
 

5. Ordering Information


TUNKIA TH3600 three-phase Energy Meters Calibrator Broadband Low Current Standard Power Source


 
Company Profile
 

TUNKIA TH3600 three-phase Energy Meters Calibrator Broadband Low Current Standard Power Source

TUNKIA TH3600 three-phase Energy Meters Calibrator Broadband Low Current Standard Power SourceTUNKIA TH3600 three-phase Energy Meters Calibrator Broadband Low Current Standard Power Source

Send your message to this supplier

*From:
*To:
*Message:

Enter between 20 to 4,000 characters.

This is not what you are looking for? Post a Sourcing Request Now

You Might Also Like

From payment to delivery, we protect your trading.
TUNKIA TH3600 three-phase Energy Meters Calibrator Broadband Low Current Standard Power Source pictures & photos
TUNKIA TH3600 three-phase Energy Meters Calibrator Broadband Low Current Standard Power Source
US $1,000-80,000 / Piece
Min. Order: 1 Piece
Gold Member Since 2021

Suppliers with verified business licenses

Secured Trading Service
Manufacturer/Factory
Plant Area
8000 square meters
Management System Certification
ISO9001:2015, ISO14001:2015, ISO45001:2016, Intellectual Property Management System Certificate, ISO 27001:2013