Customization: | Available |
---|---|
After-sales Service: | Life Time |
Warranty: | 12 months Excellent After-sales Service |
Shipping Cost: | Contact the supplier about freight and estimated delivery time. |
---|
Payment Methods: |
|
---|---|
Support payments in USD |
Secure payments: | Every payment you make on Made-in-China.com is protected by the platform. |
---|
Refund policy: | Claim a refund if your order doesn't ship, is missing, or arrives with product issues. |
---|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Voltage Sensor Test | |
Metrology Performance | Basic accuracy error |
Zero point output error | |
Full range output error | |
Linearity error | |
Return difference | |
Repeatability error | |
Influence Quantity Performance | Zero drift |
Thermal zero drift (must be equipped with temperature control box) | |
Thermal sensitivity drift (must be equipped with temperature control box) | |
Overload capacity | |
Power supply voltage impact test | |
Load change rate (must be equipped with load box) | |
Other Performance | Bandwidth measurement ( high frequency voltage source required) |
Response time (optional pulse voltage source required) |
☆ Metrology Performance Test |
|
☆ Power Supply Impact Test And Power Consumption Measurement |
Built-in DC ±(5.0 V ~ 50.0 V) adjustable power supply, which can test the power supply impact of the sensor under test.
A standard ammeter is connected in series to the power supply module loop to measure the no-load or full-load power consumption of the sensor under test. |
☆ Sensor Bandwidth Test (Optional) |
|
☆ Sensor Response Time Test (Optional) |
|
☆ Direct Display of Sensor Measurement Errors |
Advantages of the solution: The interface of the device can display the primary current output value, secondary signal measurement value, and directly display the basic error of the sensor under test and other measurement results to improve testing efficiency. |
☆Special Test Software (Optional) |
|
Measuring Range | 100 V, 200 V, 500 V, 1 kV….N kV (selected according to user needs) | |
Output Range | (10%~100%)*RG | |
Accuracy Class | Class 0.02 | Class 0.05 |
Short-term Stability (%/min) | 0.01 | 0.02 |
Measurement Uncertainty (k=2) (%*RD + %*RG) |
0.012 + 0.008 | 0.03 + 0.02 |
Adjust Fineness | 0.002%*RG | 0.002%*RG |
Display Digits | 7-digit decimal | 6-digit decimal |
Maximum Load Current | 20 mA (The specific current is related to the maximum output voltage) | |
Ripple Coefficient | ≤ 0.5% | |
Setup Time | ≤ 3 s | |
Adjustment Method | Adjust the output current value through the touch screen and host computer software | |
Protective Function | Short circuit protection, overload protection, arc protection | |
Note | RD is the reading value, RG is the range value |
Sensor Secondary Signal Measurement |
Voltage measurement range | 100 mV, 1 V, 10 V, manual or automatic shifting |
Voltage measurement scope | ±(10mV~12V) | |
Current measurement range | 10 mA, 100 mA, 1 A, manual or automatic shifting | |
Current measurement scope | ±(1 mA ~ 1.1 A) | |
Measurement uncertainty (k=2) | 0.003%*RD + 0.002%*RG | |
Display digits | 7-digit decimal | |
Temperature Coefficient | 5 ppm/°C @ (0°C~40°C) | |
Sensor Power Supply | Supply voltage | DC ±(5.0 V~50.0 V) adjustable |
Maximum load capacity | 1 A | |
Measurement uncertainty (k=2) | Voltage/Current: 0.2%, Power: 0.5% | |
Protective function | Short circuit protection, overload protection, overheating protection | |
AC power supply (customized) | AC 220 V power supply can be added according to user needs | |
Note | Sensor units can be customized |
Voltage Output Range | 10 mV~11 V |
Frequency Range | 10 Hz ~ 1 MHz |
Short Term Stability | 0.01%@40 Hz~5 kHz |
Measurement Uncertainty (k=2) | 0.02%@40 Hz~5 kHz |
Maximum Load | 10 mA |
Application | Voltage sensor bandwidth test |
Pulse | Unipolar pulse |
Output Range | 200V~2kV |
Adjust Fineness | 0.1V |
Single Pulse Width | Adjustable within the range of 1 ms ~ 10 ms |
Single Pulse Rise Time | ≤10 μs |
Application | Voltage sensor response time test |
Nominal Input Current | Two specifications: 100 mA and 1 A |
Nominal Output Voltage | 1 V |
Measurement Frequency Range | DC ~ 1 MHz |
Resistance Annual Stability | 18 ppm |
AC/DC Difference | 20 ppm @ 50 Hz,25 ppm @ 100 kHz |
Phase Difference | 5 μrad @ 50 Hz,500 μrad @ 100 kHz |
Application | Convert secondary current signals from Type I/I sensors to voltage for bandwidth or response time testing |
Power Supply | AC (220±22) V, (50±2) Hz |
Maximum Power Consumption | 200 VA |
Preheat Time | 30mins |
Working Environment | Temperature: 0°C ~ 40°C Humidity: 20%R·H ~ 85%R·H, no condensing. Others: No electromagnetic field interference. |
Storage Environment | Temperature: -20°C ~ 70°C Humidity: 10%R·H ~ 95%R·H, no condensing. |
Communication Interface | RS232×1 |